Quick answer

A service entrance conductor is one of the heavy wires that carry electricity from the point where the utility’s service drop or lateral connects to your building, through the meter, to the terminals of your main service disconnect.

They are the customer-side end of the service. Article 230 of the National Electrical Code sets their minimum size, routing and protection; the utility’s conductors upstream of the service point are outside the NEC.

Quick facts

The key facts about Service Entrance Conductor, with sources:

Runs from
The service point (splice to drop or lateral) to the service disconnect 1
Code article
NEC Article 230, Services 1
Minimum size of the feed
Service conductors: 8 AWG copper or 6 AWG aluminum; 12 AWG for limited loads 1
Overhead attachment height
At least 10 ft above finished grade 1
Ownership
Usually the customer, per utility service rules 3
Emergency disconnect (2023 NEC)
Outdoor, readily accessible, marked for one- and two-family homes 2

Key takeaways

  • Service entrance conductors are the last stretch of wire before your main breaker, and they have no breaker ahead of them in your house.
  • The service point marks the handoff: utility wire before it, your wire after it.
  • NEC Article 230 sets their size, routing and clearances.
  • Damage here is serious because only the utility’s fuse can stop a fault.
  • Replacing them is a permitted job done with the utility, usually during a panel upgrade.

What service entrance conductors are

Every home’s power arrives through a short chain. The utility’s transformer sends power through a service drop, overhead, or a service lateral, underground. At the service point, those utility conductors connect to your conductors. From there, service entrance conductors run to the meter and on to the main disconnect.

EC&M explains that a service is the conductors and equipment that connect the utility to the premises wiring, and that the service drop and lateral are utility-owned conductors from the transformer to the service point 1. Article 230 rules begin at the service point.

Upstream of all this, the utility moves power at high voltage and steps it down at substations and neighborhood transformers 4.

The last transformer makes the 120/240-volt split-phase supply your service carries: two hot legs and a grounded neutral 5.

So a typical home service has three service entrance conductors, two hots and a neutral.

On an overhead service, you can see them: a cable or conduit with a weatherhead running down the wall to the meter. On an underground service, they are hidden in conduit between the meter and panel.

How power travels through the service

  1. Utility transformer → service drop (overhead) or service lateral (underground)
  2. Service point splice → service entrance conductors → weatherhead or conduit down the wall
  3. Service entrance conductors → meter base → meter
  4. Meter → service entrance conductors → main service disconnect → panel → branch circuits
Layers Who owns what along the service
  1. Utility sideTransformer, service drop or lateral, up to the service point 1
  2. Service pointWhere utility conductors meet customer conductors 3
  3. Customer sideService entrance conductors, meter base (often), service disconnect 3
  4. Premises wiringPanel, feeders and branch circuits

Source: [1] [3]

Types of service entrance conductors

TypeDescriptionWhere used
SE cable, style U (SEU)Two insulated conductors with a bare concentric neutralOverhead service down the wall to the meter
SE cable, style R (SER)Insulated conductors plus neutral and ground in a round jacketMeter to panel or feeders
Conductors in conduitIndividual wires in rigid, IMC or PVC conduitMast services and underground 1
Underground service entrance conductorsFrom the lateral to the service equipmentBuried services; 230.30(B) lists 11 wiring methods 1

Example: overhead clearances that shape a service

Minimum clearances for overhead service conductors come from NEC 230.24 and 230.26 as summarized by Mike Holt in EC&M (April 2024) 1. Your local code edition may differ.

Where the wires passMinimum clearanceRule
Over walkable areas (120/240 V)10 ft230.24(B)
Over residential driveways and yards12 ft230.24(B)
Same areas, over 300 V to ground15 ft230.24(B)
Over streets and truck parking18 ft230.24(B)
Over railroad tracks24.5 ft230.24(B)
Above a roof (and 3 ft out from its edge)8.5 ft, with exceptions230.24(A)
Attachment point on the building10 ft above grade minimum230.26
Chart Minimum vertical clearance of overhead service conductors

Overhead service conductors must clear 10 ft over walkable areas, 12 ft over residential driveways, 15 ft for systems over 300 V to ground, 18 ft over streets and 24.5 ft over railroad tracks.

Minimum vertical clearance of overhead service conductors (feet above grade)
ItemValue (feet above grade)
Walkable areas (120/240 V) 10 ft
Residential driveways and yards 12 ft
Same, over 300 V to ground 15 ft
Streets and truck parking 18 ft
Railroad tracks 24.5 ft

Data period: NEC 230.24(B), as summarized in EC&M, April 2024

Source: [1]

A roof replacement that raises the roofline, or a new garage under the drop, can push a mast below these minimums, so the electrician may have to raise it. Our permits guide covers when service work needs one.

Where you see them

Outside on an overhead service, look for the weatherhead near the roofline and the cable or conduit running down to the meter. On an inspection report, defects may be listed as “damaged service entrance cable,” “missing drip loop” or “inadequate clearance.”

On a panel upgrade quote, “new service entrance conductors” or “new mast” means these wires are being replaced to match a larger service. Learn your current size with our service size guide.

What correct service conductors give you, and their limits

Done right

  • Sized to carry the calculated load of the home 1.
  • Protected by clearances and approved wiring methods 1.
  • Sealed where they enter the building to keep water out 1.
  • Clear ownership boundary at the service point 3.

Limits

  • No overcurrent protection on your side ahead of the main disconnect.
  • Weather, UV and tree contact wear outdoor cable over time.
  • Upsizing the service means replacing them, and often the meter base.
  • Work requires utility coordination to cut and restore power.

Rules that limit how they run

  • Service entrance conductors may not pass through one building to supply another (230.3) 1.
  • Feeder and branch-circuit wires may not share their raceway or cable (230.7) 1.
  • Trees may not support service spans (230.10) 1.
  • Generally one service per building, with listed exceptions (230.2) 1.

What drives the cost of replacing them

No dollar figures here. See panel upgrade costs for how service work is priced.

  • Service size. A larger service needs larger conductors.
  • Overhead vs underground. Trenching and conduit add labor.
  • Mast height. Clearance rules may require a taller mast 1.
  • Meter base. Often replaced at the same time.
  • Utility fees and scheduling. Disconnect and reconnect rules vary.
  • Lifespan. Outdoor cable jackets age with sun and weather; inspections catch wear.

How service conductors get replaced

Replacing service entrance conductors is licensed electrician work coordinated with the utility.

  1. Load calculation and service size decision.
  2. Permit pulled; utility notified for disconnect.
  3. Utility cuts power at the service point.
  4. Electrician replaces mast, conductors, meter base and service equipment as needed.
  5. Inspection; utility reconnects and sets the meter.

Upkeep

  • Look at the weatherhead and cable from the ground once a year.
  • Keep trees trimmed away from the service drop; call the utility for that.
  • After storms, look for a leaning mast or sagging wires.
  • Have an electrician inspect older services; see electrical inspections.

Warning signs

A cracked or frayed cable jacket, a bent mast, wires pulled from the house, water stains under the meter, or lights that dim and brighten when big loads start can point to service conductor problems.

If wires are down or sparking, stay away and call the utility and 911. For damage without immediate danger, call an emergency electrician and the utility.

No breaker protects these wires

Service entrance conductors sit ahead of your main breaker, so turning off the main does not de-energize them. Never touch the mast, weatherhead, cable or meter. Only the utility can cut power to them.

Code rules

AuthorityRuleRequirement
NFPA 70 (NEC)Article 230, 230.23 and 230.31Size for the Article 220 load; service conductors feeding them at least 8 AWG Cu / 6 AWG Al (12 AWG limited-load exception) 1
NFPA 70 (NEC)230.24, 230.26Clearances and 10 ft minimum attachment height 1
NFPA 70 (NEC)230.8Raceways entering the building sealed 1
NFPA 70 (NEC), 2023 ed.230.85Outdoor emergency disconnect at one- and two-family homes; replacements must comply 2
UtilityService requirements manualPoint of connection, ownership, metering 3

Service conductors vs related wiring

ConductorFromToOwner
Service drop / lateralUtility transformerService pointUtility 1
Service entrance conductorsService pointService disconnectCustomer, usually 3
FeederService equipmentSubpanelCustomer
Branch circuitFinal breakerOutlets and loadsCustomer

Myths

Myth Turning off the main breaker kills the service wires.
Reality They are on the supply side of the main and stay live.
Myth The utility owns everything outside the house.
Reality Ownership usually changes at the service point 3.
Myth Any heavy cable can be used.
Reality Article 230 limits wiring methods and minimum sizes 1.

State and utility differences

Your state’s NEC edition decides rules like the 2023 outdoor emergency disconnect 2. Your utility’s service manual decides the point of connection; Snohomish County PUD, for example, puts it at the mast for overhead service and at the meter base for residential underground service 3.

When this matters to you

Service entrance conductor size and condition matter when you upgrade service, add big loads, replace a roof under an overhead drop, or buy an older home. In each case, ask whether the service entrance conductors, mast and meter base are sized and in good shape.

Start with the load calculator to see whether your service is big enough.

Roof work alert

Re-roofing under an overhead service often disturbs the mast. Ask the roofer to coordinate with the utility and an electrician before work starts.

Questions about Service Entrance Conductor

What are service entrance conductors?

On an overhead service, they are the thick cable or conduit you can see running from the weatherhead down the wall into the meter, then on to the main breaker.

On an underground service they are buried or hidden in conduit. Either way they carry the full service current with no breaker of yours ahead of them.

Who is responsible for service entrance conductors?

Usually the homeowner. Ownership typically changes at the service point, where the utility’s conductors connect to yours. Snohomish County PUD, for example, puts that point at the service mast for overhead residential service and at the meter base for underground residential service. Check your own utility’s service manual.

What size are service entrance conductors?

Service entrance conductors are sized for the home’s calculated load under NEC Article 220.

The overhead or underground service conductors that feed them can be no smaller than 8 AWG copper or 6 AWG aluminum (230.23 and 230.31), except 12 AWG for limited-load installations. A 200-amp service uses much larger conductors than that minimum.

The electrician sizes them from the load calculation and the edition of the NEC your state uses.

Does turning off the main breaker shut off the service entrance wires?

No. Service entrance conductors are on the supply side of the main breaker, so they stay live when the main is off. Only the utility can de-energize them, by disconnecting at the meter or the service point. That is why work on them is coordinated with the utility.

How high must overhead service wires be?

Under NEC 230.24, overhead service conductors need at least 10 feet over walkable areas for 120/240-volt systems, 12 feet over residential driveways and yards, and 18 feet over streets. The attachment point on the building must be at least 10 feet above grade. Local codes may adopt different editions.

What is the difference between service entrance conductors and a service drop?

The service drop is the utility’s overhead wire from the pole to your house, ending at the service point. Service entrance conductors are your wires from that point to the main disconnect. The drop belongs to the utility and falls outside the NEC; the service entrance conductors fall under Article 230.

When do service entrance conductors need replacing?

When the jacket is cracked or frayed, the mast is damaged, water gets into the meter base, or the service is being upgraded to a larger size. Aging outdoor cable is common on older homes. A licensed electrician replaces them under permit, with the utility cutting and restoring power.

What is SEU and SER cable?

They are common service entrance cable styles. SEU has two insulated conductors wrapped by a bare concentric neutral and is often used down the wall to the meter.

SER has insulated conductors plus a neutral and ground in a round jacket and is often used from the meter to the panel or to feed a subpanel.

What is the 2023 NEC emergency disconnect rule?

The 2023 NEC Section 230.85 requires one- and two-family homes to have an emergency disconnect in a readily accessible outdoor location, on or within sight of the home, marked “EMERGENCY DISCONNECT.” When service equipment is replaced, the rule applies, so a service upgrade may add an outdoor disconnect.

Sources

  1. Mike Holt, NEC Requirements for Services, Part 1, EC&M (April 16, 2024), retrieved .
  2. Larimer County (CO), 2023 NEC Significant Code Changes, retrieved .
  3. Snohomish County PUD, Electric Service Requirements, Section 2: General Requirements, retrieved .
  4. U.S. EIA, Electricity explained: Delivery to consumers, retrieved .
  5. Energy Education (University of Calgary), Distribution transformer, retrieved .

Expert review

Written by the HyreElectrical Research team. Not yet reviewed by an outside expert. We say so rather than imply a review that has not happened; see our editorial policy.

How the numbers were checked: Code facts checked against Mike Holt’s Article 230 summary in EC&M and Larimer County’s 2023 NEC summary; ownership against Snohomish County PUD’s service requirements; supply chain against EIA and Energy Education on 2026-10-10.