HyreElectrical

Original research · Electrification

The Induction Circuit Nobody Mentions

The gas-stove debate is conducted almost entirely without reference to whether the kitchen has the circuit. RECS counts the fuel; NEC Table 220.55 and 210.19(A)(3) size the circuit that fuel does or does not require. Nobody had joined them, by tenure and by Census division, until now.

Updated September 6, 2026 · Data as of 6 September 2026

Written by HyreElectrical Research Desk Primary-source research and fact checking

39.50M homes cook on gas or propane 32.0% of the US housing stock — EIA RECS 2020
53.1% of US homes cook on electricity induction and resistance ranges counted together, not separately
20.3 pts wider electric-range gap in apartments renter- vs owner-occupied, same housing type
36.0 pts spread across nine Census divisions East South Central (highest) minus Middle Atlantic (lowest)

The finding

34.68 million US homes — 28.1% of the housing stock — cook on natural gas, and a further 4.82 million (3.9%) on propane, according to the US Energy Information Administration’s 2020 Residential Energy Consumption Survey. Combined, 39.50 million homes (32.0%) have no obvious reason to already carry a 240-volt branch circuit at the range, because a gas or propane range’s only electrical load, where it has one at all, is a small 120-volt draw for an igniter or a clock. HyreElectrical calculation: an induction range is, electrically, the same appliance as a full-size electric-resistance range — both are sized under NEC Table 220.55 and wired under 210.19(A)(3) onto a dedicated 240-volt circuit, and RECS records neither one separately; both sit inside its single “Electricity” category. So for roughly a third of US kitchens, installing an induction range is circuit work before it is an appliance purchase — and the remaining 5.26 million dual-fuel homes (4.3%) are a genuinely unresolved middle case this page does not force into either column. HyreElectrical does not perform, supervise or warrant electrical work.

Read this before the numbers: what this page counts, and does not

RECS defines a “range” as a unit with both an oven and a cooktop. Homes running a separate wall oven and a separate cooktop — 19.40 million and 17.52 million respectively — sit in different rows of the same table and are excluded from every figure on this page, because they are two circuits, not one, and folding them in would misstate the range population this page is actually about.

RECS 2020 does not separately identify induction ranges. Its “Most-used range fuel” field has four values — Electricity, Natural gas, Propane, Dual-fuel — and an induction range is counted inside “Electricity” alongside a conventional electric-resistance range. No federal table anywhere counts induction ranges specifically. This page treats induction and resistance as electrically equivalent for circuit purposes (see the calculation section for why that is a defensible assumption, not a measured fact) and states the limitation once here.

This is a fuel count, not a circuit inventory. No national survey asks whether a specific gas-heated kitchen happens to have a spare 240-volt circuit nearby — a dryer or an EV charger circuit in an adjoining laundry or garage wall is a real, if unmeasured, coincidence in some homes. The population sized below is a scope calculation, not a per-home prediction.

Nothing here rests on HyreElectrical’s own contractor store. That store is five states and 74% Florida; it has no bearing on a national federal survey and plays no part in any figure on this page.

How the US cooks, 2020

How the US cooks, 202053.1%Electricity — 66 million homes28.1%Natural gas — 35 million homesDual-fuel — 5 million homesPropane — 5 million homes10.7%No range — 13 million homesEIA RECS 2020, Table HC3.1, retrieved 6 September 2026.
32.0% of US homes cook on gas or propane — the population with no existing reason to carry a 240-volt range circuit. EIA RECS 2020, Table HC3.1, retrieved 6 September 2026. Percentages are HyreElectrical calculations from the published counts.

Source fact. Of 123.53 million US housing units, 110.32 million have a range. Of those, the EIA’s 2020 Residential Energy Consumption Survey found 65.56 million (53.1% of all US homes) cook mainly on electricity, 34.68 million (28.1%) on natural gas, 5.26 million (4.3%) on a dual-fuel range, and 4.82 million (3.9%) on propane. A further 13.21 million homes (10.7%) have no range at all, most of them relying on a separate cooktop, a separate oven, or neither.

Most-used range fuelHomes (millions)Share of US homes
Electricity65.5653.1%
Natural gas34.6828.1%
Dual-fuel5.264.3%
Propane4.823.9%
No range13.2110.7%
Gas + propane (this page’s base scope)39.5032.0%

Rows may not sum to exactly 123.53 million because of independent rounding to the hundredth of a million in EIA’s own tables. “Dual-fuel” means one range with a gas cooktop and an electric oven; see the calculation section for why it is not added to either side of this page’s scope figure.

Why cooking fuel is a wiring question before it is a shopping question

A gas or propane range’s electrical demand, where it has any at all, is a 120-volt load for an electronic igniter, a clock or a control board — the kind of draw a standard wall receptacle or a hard-wired 120-volt connection already handles. Nothing about installing or owning one gives an electrician a reason to also run a 240-volt circuit to that wall.

An electric range — whether induction or electric-resistance — is a different electrical animal. Under NEC Table 220.55, a single household range is assigned a demand load for circuit-sizing purposes (8 kW for a range rated up to 12 kW, the figure this site’s electrical load calculator already publishes), and 210.19(A)(3) ties the branch-circuit conductor’s minimum rating to that demand rather than to the appliance’s full nameplate rating. HyreElectrical calculation. At 240 volts, an 8 kW demand load draws 33.3 amps — above the 30-amp standard breaker size and below the 40-amp one — which is why a household range circuit is built at 40 amps at minimum, and commonly at 50 amps once a range’s nameplate rating runs above 12 kW, which many modern ranges with double ovens or higher-wattage elements do. Confirming which of the two a specific installation needs is a calculation a licensed electrician runs from the actual nameplate — this page states the code structure that produces the two numbers, not a substitute for that calculation.

The assumption behind treating induction and resistance ranges alike, stated plainly. NEC Table 220.55 and 210.19(A)(3) size a household range by its nameplate kilowatt rating; neither article distinguishes the technology that produces the heat. An induction range that draws 8–11 kW at full nameplate is sized exactly as a resistance range at the same rating would be. That is a reasonable reading of how the code is structured, not a measurement of every induction model on the market — RECS gives us no way to check it against actual induction nameplates, because RECS does not know which of its “Electricity” homes have an induction range at all.

The calculation: three fuel-scope widths, and the case RECS cannot resolve

The three fuel-scope widths are HyreElectrical’s own arithmetic on top of the RECS counts above — not a figure EIA publishes. The method and its limits are both stated in full so the number can be checked and disagreed with.

The population, at three fuel-scope widths

Narrow (natural gas only): 34.68 million homes, 28.1% of the stock. The single largest population with a definite reason to lack a 240-volt range circuit.

Base (gas + propane): 39.50 million homes, 32.0%. This is the figure used throughout the rest of this page. Both fuels share the identical electrical fact: neither requires or typically receives a 240-volt branch circuit at the range.

Broad (+ dual-fuel): 44.76 million homes, 36.2%. Included only as an upper bound. It is very likely an overstatement — see the next block for why.

Why dual-fuel is reported separately, not summed in

A dual-fuel range pairs a gas cooktop with an electric oven in one appliance. Whether that oven already needs, or already has, a 240-volt circuit varies by model: some manufacturers specify a 120-volt connection for the electric oven cavity; others, particularly larger or self-cleaning models, specify 240 volts. No federal table records which is more common, and this site has not surveyed range installation manuals to build that count ourselves. Folding the 5.26 million dual-fuel homes into the “needs a new circuit” population, as the broad figure does, therefore likely overstates the true number — but excluding them entirely would understate it for the share of dual-fuel ovens that are 120-volt only. We report the range rather than guess a split.

What this figure is not

It is not a claim that every one of these 39.50 million homes will convert to induction, and it is not a forecast of adoption. It is not a cost estimate — that lives on our panel-upgrade cost page, not here. And it is not a claim that a spare 240-volt circuit is impossible near any of these ranges: a nearby dryer circuit or a garage EV-charger run is a real, if unmeasured, coincidence in some kitchens. Even there, extending or sharing an existing 240-volt circuit for a range is a calculation for a licensed electrician, never a do-it-yourself repurposing.

What the branch-circuit arithmetic actually looks like

Source fact, HyreElectrical calculation. The demand figure in the first row is the one already published on this site’s electrical load calculator, cited to the same NEC table there. The remaining rows are arithmetic on that figure, not additional code text.

StepWhat it isValue
1. Nameplate ratingA common household electric range, at or below the 12 kW threshold in NEC Table 220.5512 kW
2. Table 220.55, Column C demandThe load used to size the branch circuit — not the full nameplate rating8 kW
3. Minimum circuit ampacity8,000 W ÷ 240 V33.3 A
4. Standard branch-circuit ratingThe next standard overcurrent-device size at or above the minimum, per NEC Table 210.24’s standard ampere ratings40 A (minimum) or 50 A (common, especially above 12 kW nameplate)

NEC Table 220.55 and 210.19(A)(3), described here as a model code, not quoted verbatim. Adoption and amendment of the National Electrical Code is local — confirm the adopted edition and any amendments with the authority having jurisdiction, and treat the final circuit size as a licensed electrician’s determination from the actual appliance nameplate, not this table.

The tenure split — and where it runs the opposite way from this site’s panel study

Electric-range share, owner-occupied vs renter-occupied, by housing type owner-occupied %    renter-occupied %0.017.334.551.869.1Single-family & mobile homes+8.6 ptsApartments+20.3 pts% of each cell’s stock cooking on electricity
Electric-range share, owner-occupied vs renter-occupied, split by housing type. The renter gap is wider in apartments (20.3 points) than in single-family and mobile homes (8.6 points), but runs the same direction in both. HyreElectrical calculation from EIA RECS 2020, Table HC3.2, retrieved 6 September 2026.

Nationally, 63.4% of renter-occupied homes cook on electricity against 48.0% of owner-occupied homes — renters are markedly more likely to already have the 240-volt circuit an induction range needs, not less. That is the opposite direction from this site’s earlier renter-electrification-gap study, which found renters modestly over-represented in the hazard-era housing stock a panel upgrade would target. HyreElectrical analysis. The two findings are not in tension — they describe different equipment. A renter is more likely to already have the circuit an induction range needs and, separately, more likely to live in a home whose panel dates from the hazard era the earlier study measured. Both can be true at once, and this page reuses that study’s tenure framing rather than re-deriving it — see its methodology for the split-incentive argument, which applies here as much as it does to a panel.

RECS lets the tenure gap be checked against a mechanism, not just observed: Table HC3.2 splits owner and renter status separately for single-family/mobile homes and for apartments. In both housing types, renter-occupied units run a higher electric-range share than owner-occupied units of the same type — 56.7% versus 48.1% for single-family and mobile homes, and 66.4% versus 46.1% for apartments. HyreElectrical analysis. Part of the national renter/owner gap is simple composition: renters concentrate more in apartments, and apartments of every tenure run more electric than single-family homes (67.5% electric in buildings of five or more units against 48.3% in detached single-family homes, per Table HC3.1) — likely because multi-unit buildings are less often built with individual gas service. But the gap persists within each housing type too, and this page has not decomposed how much of the national figure owes to composition versus a within-type difference. Both effects point the same direction, which is the finding worth carrying, not a single decomposed percentage.

Where the gas and propane kitchens are: all nine Census divisions

Share of homes cooking on electricity, by Census division0East South Central71.5%South Atlantic70.3%West North Central64.0%Mountain57.0%New England54.3%West South Central52.0%East North Central47.5%Pacific36.8%Middle Atlantic35.5%EIA RECS 2020, Tables HC3.7 and HC3.8, retrieved 6 September 2026. Bars show each division’s electric-range shareminus 50 percentage points; the printed number is the true share.
East South Central runs 71.5% electric; Middle Atlantic runs 35.5%. A 36-point spread across nine divisions — wider than this page’s national gas-plus-propane share alone suggests. HyreElectrical calculation from EIA RECS 2020, Tables HC3.7 and HC3.8, retrieved 6 September 2026.

Source fact, HyreElectrical calculation. Sorted by electric-range share, the divisional pattern broadly echoes this site’s earlier water-heating fuel study — the South again runs most electric, the Northeast and Pacific least — which is consistent with natural-gas distribution infrastructure being historically thinner in parts of the South, a plausible driver this page has not tested against pipeline data.

Census divisionHomes (millions)Cook on electricityShare electricGas + propaneShare gas + propane
East South Central7.385.2871.5%1.1415.4%
South Atlantic24.8417.4770.3%4.2717.2%
West North Central8.505.4464.0%2.1024.7%
Mountain9.225.2657.0%2.7529.8%
New England5.883.1954.3%1.9633.3%
West South Central14.627.6052.0%3.9026.7%
East North Central18.558.8147.5%7.5740.8%
Pacific18.516.8236.8%7.7742.0%
Middle Atlantic16.045.7035.5%8.0450.1%

EIA RECS 2020, Tables HC3.7 (Northeast, Midwest) and HC3.8 (South, West), retrieved 6 September 2026. Mountain North and Mountain South are combined into one Mountain division to match the other eight.

East South Central (71.5%) and South Atlantic (70.3%) are the only divisions above 70% electric. Middle Atlantic (35.5%) and Pacific (36.8%) are the only divisions below 40%. Every other division falls between 47% and 65% electric — genuinely mixed territory, not a clean regional binary.

By year built: gas and propane share falls, then rises again

Source fact, HyreElectrical calculation. Splitting the national count by year of construction shows the gas-plus-propane share falling from the oldest housing to a low point in the 1980s, then climbing back through the newest construction band. We are not going to guess at why — a swing toward all-electric marketing in some decades, local gas-hookup costs, and regional building booms could each plausibly contribute, and untangling them needs data this table does not carry. The pattern is the finding; the explanation is not.

Before 195047.4%
20.26M homes
1950–195940.5%
12.48M homes
1960–196933.6%
12.76M homes
1970–197926.1%
18.34M homes
1980–198922.6%
16.30M homes
1990–199927.9%
17.16M homes
2000–200927.2%
16.16M homes
2010–201528.8%
5.53M homes
2016–202029.4%
4.56M homes
Year builtHomes (millions)Gas + propane (millions)Share gas + propane
Before 195020.269.6147.4%
1950–195912.485.0640.5%
1960–196912.764.2933.6%
1970–197918.344.7826.1%
1980–198916.303.6822.6%
1990–199917.164.7827.9%
2000–200916.164.3927.2%
2010–20155.531.5928.8%
2016–20204.561.3429.4%

EIA RECS 2020, Table HC3.3, retrieved 6 September 2026.

The 1980–1989 band is the low point at 22.6% gas or propane. The newest band measured, 2016–2020, is back up to 29.4% — higher than every band built between 1970 and 2015. A gas range is still a common choice in brand-new US homes, not a legacy fixture being phased out on a straight line.

What a homeowner can check before calling anyone

  1. 1
    Read the nameplate on your current range, if you have an electric one

    The rating plate — usually on the back edge, behind a drawer, or on the door jamb — states the nameplate kilowatt or watt rating and the voltage. A rating above 12 kW is the signal that a 50-amp circuit, not the 40-amp minimum, is the relevant number for this site’s load calculator.

  2. 2
    Look at the receptacle, not just the outlet cover

    A standard 120-volt duplex outlet cannot serve an electric range. A dedicated range receptacle — commonly a round three-prong or a block-shaped four-prong outlet set into the wall — is the visual signal that 240 volts already reaches that location. A gas range commonly sits in front of an ordinary 120-volt outlet or none at all.

  3. 3
    Check the panel directory for a labelled range circuit

    The panel door directory should list a circuit for the range, typically shown as a 40-amp or 50-amp double-pole breaker. An unlabelled or missing entry is not proof one does not exist, but a clearly labelled one is useful evidence before anyone quotes new work.

  4. 4
    Get the manufacturer’s installation manual for the specific range you want

    Model number, not category, decides the circuit an induction or electric range actually needs — the same rule this site’s appliance-circuit tool applies to every appliance. Two ranges of similar size can carry different nameplate ratings and, on a range above 12 kW, different minimum circuit sizes.

  5. 5
    Stop there, and get a licensed electrician for anything past looking

    Confirming, extending or adding a 240-volt circuit is licensed electrical work with a permit attached in most jurisdictions — not a do-it-yourself outlet swap. This page ends at what a homeowner can observe; the load calculation and the installation are an electrician’s job.

Limitations

  • RECS does not identify induction ranges at all

    Every figure labelled “electric” on this page includes both induction and electric-resistance ranges, because no federal survey separates them. The equal-circuit treatment of the two technologies is a reading of NEC’s rating-based structure, not a measurement of actual induction nameplates.

  • This is a fuel count, not a circuit inventory

    No survey asks whether a specific gas-heated kitchen happens to have a spare 240-volt circuit nearby. The 39.50 million figure is the population with no existing reason to have one — not a home-by-home measurement, and not a forecast of who converts.

  • Dual-fuel is reported, not resolved

    Whether a dual-fuel range’s electric oven needs 120 or 240 volts varies by model and is not recorded by RECS or by any source this page checked. The 5.26 million dual-fuel homes sit in the broad upper-bound figure only, flagged as a likely overstatement.

  • No state-level breakdown, because RECS 2020’s public tables do not support one

    Division is the finest published geography in this table set, the same limit this site’s water-heating fuel study documents for the same survey.

  • The renter/owner gap is not decomposed

    This page shows the tenure gap holds both nationally and within each housing type, but has not calculated how much of the national gap is composition (renters concentrating in more-electric apartment buildings) versus a genuine within-type difference.

  • The circuit-size table describes code structure, not a specific building’s calculation

    The 40-amp and 50-amp figures follow from NEC Table 220.55 and 210.19(A)(3) as commonly applied, described here without quoting the article text verbatim. Adopted NEC editions and local amendments vary by jurisdiction; a licensed electrician’s calculation on the actual nameplate governs, not this page.

Method

Sources. US Energy Information Administration, 2020 Residential Energy Consumption Survey: Table HC3.1 (appliances by housing unit type, for the national total), Table HC3.2 (appliances by owner/renter status, cross-tabbed with housing unit type), Table HC3.3 (appliances by year of construction) and Tables HC3.7 and HC3.8 (appliances by Census division). All five downloaded directly from eia.gov/consumption/residential/data/2020/hc/pdf/ on 6 September 2026.

Derivation. “Base scope” sums the published Natural gas and Propane rows for each geography and cross-tab. “Narrow” is the Natural gas row alone. “Broad” adds the Dual-fuel row, flagged as a likely overstatement in the text above. Division, tenure and era percentages divide each row’s relevant sum by that row’s total housing-unit count, both taken directly from the same EIA tables. The branch-circuit arithmetic (Table 220.55 Column C demand of 8 kW for a range at or below 12 kW nameplate, divided by 240 volts) reproduces the figure already published on this site’s electrical load calculator; it is not independently re-derived here.

What is not a measurement. The claim that induction and electric-resistance ranges carry the same branch-circuit requirement follows from how NEC Table 220.55 and 210.19(A)(3) are structured — by nameplate rating, not by heating technology — and is stated as HyreElectrical’s reading of that structure, not as a survey of induction range nameplates, which does not exist publicly at a national level.

Reproducibility. Every EIA figure on this page is read directly off a public table with no interpretation applied before the sums shown here. Anyone with the same five files can rebuild every row.

Questions

How many US homes cook with gas?
According to the EIA’s 2020 Residential Energy Consumption Survey, 34.68 million US homes — 28.1% of the housing stock — use natural gas as their most-used range fuel. Add 4.82 million propane homes and the combined gas-or-propane population is 39.50 million homes, 32.0%.
What percentage of US homes cook with electricity?
53.1% nationally (65.56 million of 123.53 million homes), per EIA RECS 2020. That figure covers both induction and electric-resistance ranges together — RECS does not separately identify induction ranges in any published table.
Does an induction range need a special circuit?
Yes, the same one a full-size electric-resistance range needs: a dedicated 240-volt branch circuit, typically 40 or 50 amps, sized under NEC Table 220.55 and 210.19(A)(3) by the range’s nameplate rating rather than its heating technology. A gas or propane range’s own electrical draw never justified running that circuit in the first place.
How many US homes would need new circuit work to switch to an induction range?
HyreElectrical calculates a base figure of 39.50 million homes — those currently cooking on gas or propane — as the population with no existing reason to already have a 240-volt range circuit. Narrowed to natural gas alone it is 34.68 million; a broader figure that adds 5.26 million dual-fuel homes (44.76 million) is published as a likely overstated upper bound, because whether a dual-fuel range’s electric oven already needs 240 volts varies by model.
Are renters or owners more likely to already have an electric range?
Renters. 63.4% of renter-occupied homes cook on electricity against 48.0% of owner-occupied homes, and the gap holds within both single-family/mobile homes (56.7% vs 48.1%) and apartments (66.4% vs 46.1%). That runs the opposite direction from this site’s renter-electrification-gap study, which found renters more exposed to hazard-era electrical panels — the two findings describe different equipment and are not in tension.
Which part of the US cooks most on electricity?
The East South Central Census division (Kentucky, Tennessee, Alabama, Mississippi) at 71.5% electric, narrowly ahead of South Atlantic at 70.3%, per EIA RECS 2020.
Which part of the US cooks least on electricity?
Middle Atlantic (New York, New Jersey, Pennsylvania) at 35.5% electric, with Pacific (California, Oregon, Washington, Alaska, Hawaii) close behind at 36.8% — a 36-point spread against the highest division.
Does this study break the data down by state?
No. EIA RECS 2020’s public summary tables report the nine Census divisions as their finest geography for this cross-tab, the same limit this site’s water-heating fuel study documents for the same survey.
Is a dual-fuel range already wired for 240 volts?
It depends on the specific range, and no federal source records the split. A dual-fuel range’s gas cooktop needs no 240-volt circuit; its electric oven might, depending on the model and manufacturer. This page reports the 5.26 million dual-fuel homes separately rather than assuming an answer, and includes them only in its upper-bound broad figure.

Written and audited by

HyreElectrical Research Desk

Primary-source research and fact checking

We read the model code, the federal safety notice, the municipal fee sheet or the utility tariff ourselves, and we publish the figure with the document it came from and the date we retrieved it. Where a number cannot be traced to a primary source, we publish the shorter page and say what we could not verify. HyreElectrical does not perform, supervise or warrant electrical work. Authorship is organisational: this desk, not a named persona.

10
long-form launch pages in this layout
5
states with verified licence records
16,369
electrical companies in those records
74%
of the store is Florida — disclosed first, not footnoted

How this desk works

  • Primary sources only. Code statements come from NFPA 70 as the model code. Safety statements come from CPSC. Permit fees come from the city or county fee sheet. Utility charges come from the filed tariff. We do not cite a blog that cites a source; we open the source.
  • Our contractor store is five states, and 74% of it is Florida. Any figure built on that store is titled to those states and names the concentration in the first screen. It is not a national sample of electricians.
  • Load calculations on this site are a published simplification in the shape of NEC 220.82 — first 10 kVA at 100%, remainder at 40%, HVAC at 100%, EVSE at 125%. They are labelled as not a stamped calculation. A licensed electrician using the adopted edition does that work.
  • No national price for a panel upgrade is shipped. Labour rates, the adopted code edition, whether the utility is involved, and the state of the existing wiring move the invoice too far for a roundup to help. Cost intent lives on the cost page; this page explains the decision.
  • We do not perform electrical work, and we take no payment for placement, ranking or a favourable mention. Nobody buys a position on this site.

Data as of 6 September 2026. Authorship on this site is organisational: the analysis belongs to the desk rather than to a named individual, and we do not publish credentials we do not hold. Our editorial policy sets out how we source, date and correct what we publish.

Sources & retrieval dates

  1. US Energy Information Administration — 2020 Residential Energy Consumption Survey, Table HC3.1 (Appliances in U.S. homes, by housing unit type) , The national range-fuel split: 65.56 million homes on electricity, 34.68 million on natural gas, 5.26 million dual-fuel, 4.82 million propane, and 13.21 million with no range, out of 123.53 million total housing units. Retrieved 6 September 2026.
  2. US Energy Information Administration — 2020 RECS, Table HC3.2 (Appliances in U.S. homes, by owner or renter status) , Range fuel cross-tabbed with tenure and housing unit type, used for the tenure and housing-type findings. Retrieved 6 September 2026.
  3. US Energy Information Administration — 2020 RECS, Table HC3.3 (Appliances in U.S. homes, by year of construction) , The nine construction-era bands and their range-fuel splits used in the era table and chart. Retrieved 6 September 2026.
  4. US Energy Information Administration — 2020 RECS, Table HC3.7 (Appliances in U.S. homes in the Northeast and Midwest regions) , New England, Middle Atlantic, East North Central and West North Central division figures. Retrieved 6 September 2026.
  5. US Energy Information Administration — 2020 RECS, Table HC3.8 (Appliances in U.S. homes in the South and West regions) , South Atlantic, East South Central, West South Central, Mountain (North and South) and Pacific division figures. Retrieved 6 September 2026.
  6. National Fire Protection Association — NFPA 70, National Electrical Code, code development page , Cited for NEC Table 220.55 (household range demand factor) and 210.19(A)(3) (branch-circuit rating tied to that demand), described here as a model code and not quoted verbatim. Adoption and amendment is local. Retrieved 6 September 2026.

Switching from gas to induction?

Size the electrical work before the appliance. Tell us where the house is and what it currently runs on, and we will connect you with licensed electrical companies in your area.

Check your load calculation See panel-upgrade costs

HyreElectrical does not perform, supervise or warrant electrical work, and takes no payment for placement, ranking or favourable mention. This is research on published federal survey data, not advice on a specific property or appliance. Every fuel-scope figure is a scope calculation, not a forecast of how many households will convert. We have no commercial relationship with EIA, any range manufacturer, or the National Fire Protection Association.