Questions this calculator answers
- Is 3% voltage drop a code requirement?
- No. The 3% branch-circuit and 5% total figures appear in informational notes to NEC 210.19(A) and 215.2(A), which are explanatory and not enforceable. A branch circuit over 3% is generally not a violation on that basis alone, though it may still be poor design that works badly.
- Then why does it matter?
- Because excessive drop is a real performance problem even when it is legal. Motors start poorly and run hot, heating elements underperform, and long high-current loads waste energy as heat. Knowing it is a recommendation lets you weigh the cost of fixing it instead of treating it as mandatory.
- How accurate is this calculation?
- It is a simplified DC-resistance approximation from NEC Chapter 9 Table 8, ignoring reactance, power factor, temperature rise and conduit material. For ordinary residential branch circuits it is close enough to decide with; for large feeders or poor power factor, the real figure differs and an electrician should run it.
- Should I enter one-way or round-trip length?
- One-way — the distance from the panel to the load. The tool doubles it internally for a single-phase circuit, because the current travels out and back. Entering round-trip length will double your answer.
- Why does 240 V help so much?
- The same conductor carrying the same load loses the same volts, but at 240 V that loss is measured against twice the voltage. Our base case loses 6.34 V either way: 5.28% of 120 V, 2.64% of 240 V. Where a load can run at 240 V, the percentage drop halves at no extra cost.
- Why is aluminum so much worse at the same size?
- Lower conductivity means higher resistance for the same physical size. Our 12 AWG base case goes from 5.28% in copper to 8.48% in aluminum over the same run at the same load. Aluminum feeders are common and perfectly legitimate; they are simply sized larger for the same job.
- Does a large voltage drop damage anything?
- It can, indirectly. Motors are the main concern — low voltage at start means high current, which means heat and shortened life. Heating elements simply underperform. Electronics with switching supplies are largely tolerant. The damage case is real but it is specific to motor loads rather than general.
- My electrician says the run has to be upsized to meet code. Is that right?
- If voltage drop is the reason, the "to meet code" part is usually wrong, because those figures are recommendations. The advice to upsize may still be sound, especially for a motor or a long run to a detached building. Ask which it is: compliance or engineering judgment you can weigh on cost.
- Can I use this to plan my own wiring?
- No. Live electrical work is not a do-it-yourself subject here, and nothing on this site is a stamped calculation, a design or a permit document. This screens a run so you can understand a proposal or ask a better question; the design comes from someone who has seen the building and signs for it.
Sources and methodology
Figures dated 5 September 2026. Last reviewed .
- NFPA 70, National Electrical Code — 210.19(A) and 215.2(A) informational notes, and Chapter 9 Table 8 (National Fire Protection Association, retrieved 2026-09-05. Source for the 3% branch and 5% total voltage-drop figures being informational notes rather than requirements, and for the DC resistance values used in the calculation. NFPA provides free read-only access to the code text.)
- NEC adoption maps — which edition is enforced where (National Fire Protection Association, retrieved 2026-09-05. Adoption and amendment of the National Electrical Code is local. A state or city may be on an older edition, may amend it, and may add rules of its own. Confirm the adopted edition and the amendments with the authority having jurisdiction before relying on any code figure here.)