Questions this calculator answers
- What size wire do I need for a 20 amp circuit?
- 12 AWG copper, in the ordinary case. Table 310.16 lists it at 25 A at 75 °C, but NEC 240.4(D) caps its overcurrent protection at 20 A, which is why the standard 20 A branch circuit is a 12 AWG circuit. That cap overrides both the table and the next-size-up allowance.
- Why does the tool default to 75 °C and not 90 °C?
- Because under NEC 110.14(C) the rating of the equipment you terminate on generally governs, and much equipment rated 100 A or less has 60 °C terminations. The 90 °C column is mostly for derating arithmetic, not breaker selection. Treat a 90 °C answer with suspicion unless the terminations are confirmed.
- Does this apply derating?
- No, and that is a deliberate limitation stated on the output itself. More than three current-carrying conductors in a raceway reduces allowable ampacity, and so does an ambient above the 30 °C the table assumes — an attic in summer is not 30 °C. Treat every figure here as a ceiling before those adjustments.
- Can I use this to wire a circuit myself?
- No. Live electrical work is not a do-it-yourself subject here, and nothing on this site is a stamped calculation, a design or a permit document. This is a screening tool for understanding a proposal or checking why an electrician specified a size, not instructions.
- Is a 20 A breaker on 14 AWG wire a problem?
- Yes, and it is a common finding in older work. NEC 240.4(D) limits 14 AWG copper to a 15 A device. A 20 A breaker on 14 AWG conductors removes the protection the conductor depends on, and it is one of the defects worth having an electrician look at rather than living with.
- Why is aluminum capped lower than copper at the same size?
- Aluminum conducts less well, so the same size carries less current: 10 AWG aluminum is capped at 25 A against copper's 30 A. Aluminum branch wiring also has its own termination and connection history, a larger subject to raise with an electrician than to settle from a table.
- Which NEC edition are these values from?
- The Table 310.16 ampacities and 240.4(D) caps here were corroborated against two independent published references on 2026-09-05. Code adoption is local: a state or city may use an older edition, amend it, or add rules. Confirm the adopted edition with your building department before relying on any figure.
- The tool says one size and my electrician specified another. Who is right?
- Probably your electrician, and the useful move is to ask which factor drove it. Derating, ambient, termination temperature, run length, future load and the manufacturer’s installation instructions can each push the answer up, and this screen sees none of them. A specific answer to that question is easy for a competent electrician to give.
Sources and methodology
Figures dated 5 September 2026. Last reviewed .
- NFPA 70, National Electrical Code — Article 310 (conductor ampacity) and 240.4(D) (small conductors) (National Fire Protection Association, retrieved 2026-09-05. The code articles this tool screens against. NFPA holds the text and provides free read-only access. Ampacity values and the 240.4(D) caps used here were corroborated against two independent published references; verify against the edition your jurisdiction enforces.)
- NEC adoption maps — which edition is enforced where (National Fire Protection Association, retrieved 2026-09-05. Adopted editions differ by state and several states delegate adoption to local jurisdictions. Basis for the local-adoption caveat repeated on this page.)